| Shareholders | E.ON Energy from Waste AG (85%) GP Papenburg-Entsorgungs-GmbH (15%) | | Commissioning | 2005 | | Technical incineration capacity | 280,000 t/a | | Incineration lines | 2 | | Calorific value of waste | 8-17.5 MJ | | Combustion temperature | > 850°C | | Live steam pressure | 40 bar | | Live steam temperature | 400°C | | Live steam output per boiler | 58.8 MW | | Combustion heat output per boiler | 52.5 MW | | Maximum electric current generation | 27.4 MW | | District heating (currently optional) | 15 MW |
| |
|